46 Digistart IS User Guide
www.controltechniques.com Issue: 4
Application
Parameter
Pr Number
Suggested value
Compressor Screw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
1A
2A
2D
2B
Model dependent
Constant Current
5 seconds
400%
Compressor Recip
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
1A
2A
2D
2B
Model dependent
Constant Current
5 seconds
450%
Conveyor
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
1A
2A
2D
2B
2H
2K
2I
Model dependent
Constant Current
5 seconds
400%
Adaptive Control
Constant Deceleration
10 seconds
Crusher Rotary
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
1A
2A
2D
2B
5A
1C
Model dependent
Constant Current
10 seconds
400%
30 seconds
20 seconds
Crusher Jaw
Motor Full Load Current
Start Mode
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
1A
2A
2D
2B
5A
1C
Model dependent
Constant Current
10 seconds
450%
40 seconds
30 seconds
8.6 Standard menu
The standard menu provides access to commonly used parameters. For parameter details, see Parameter Descriptions on page 51.
Table 8-3 Standard menu
Parameter Group
Parameters
Default Value
1 - Primary Motor Set
M
1A
Motor Full Load Current
Model dependent
2 - Start/Stop Modes-1
M
2A
Start Mode
Constant Current
2B
Current Limit
350%
2C
Initial Current
350%
2D
Start Ramp Time
00:10 (minutes:seconds)
2H
Stop Mode
Coast to Stop
2I
Stop Time
00:03 (minutes:seconds)
2O
Auto-Start Type
Off
2P
Auto-Start Time
00:01 (hours: minutes)
2Q
Auto-Stop Type
Off
2R
Auto-Stop Time
00:01 (hours: minutes)
3 - Digital Inputs
M
3A
Input A Function
Emergency Stop
3B
Input A Name
Emergency Stop
3C
Input A Trip
Always Active
3D
Input A Initial Delay
00:00 (minutes:seconds)
3E
Input A Trip Delay
00:00 (minutes:seconds)
3F
Input B Function
Input Trip (N/O)
3G
Input B Name
Input Trip
3H
Input B Trip
Always Active
3I
Input B Initial Delay
00:00 (minutes:seconds)
3J
Input B Trip Delay
00:00 (minutes:seconds)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Digistart IS1x0043B series and is the answer not in the manual?

Emerson Digistart IS1x0043B series Specifications

General IconGeneral
BrandEmerson
ModelDigistart IS1x0043B series
CategoryController
LanguageEnglish

Related product manuals