8.8 Parameter descriptions
8.8.1 Notes on optional parameters
The following sections provide a description for all the parameters, whether available by default or optional. Optional parameters are
only available if the relevant option card is fitted to the soft starter. For a detailed list of optional parameters, refer to the table below.
Table 8-5 Optional parameters
No
Function
Option card required
3K
Input C Function
NOTE
Inputs C and D are only available if the input/output expansion card
is installed.
3L
Input D Function
4J
Relay D Action
NOTE
Outputs D, E and F are only available if the input/output expansion
card is installed.
4K
Relay E Action
4L
Relay F Action
5K
Ground Fault Level
NOTE
Ground fault protection is only available if the RTD/PT100 and
ground fault protection card is fitted.
6H
Ground Fault Delay
8A
Analog Input Trip
NOTE
The analog input is only available if the input/output expansion card
is installed.
8B
Analog Input Scale
8C
Analog Trip Point
8H
Analog Output B
NOTE
Analog Output B is only available if the input/output expansion card
is installed.
8I
Analog B Scale
8J
Analog B Maximum Adjustment
8K
Analog B Minimum Adjustment
14B
RTD/PT100 B °C
NOTE
PT100 inputs B to G are only available if the RTD/PT100 and
ground fault protection card has been installed.
14C
RTD/PT100 C °C
14D
RTD/PT100 D °C
14E
RTD/PT100 E °C
14F
RTD/PT100 F °C
14G
RTD/PT100 G °C
16P
Ground Fault
NOTE
Ground Fault and PT100 inputs B to G are only available if the
RTD/PT100 and ground fault protection card has been installed.
16R
RTD/PT100 B
16S
RTD/PT100 C
16T
RTD/PT100 D
16U
RTD/PT100 E
16V
RTD/PT100 F
16W
RTD/PT100 G
8.8.2 Group 1 - Primary motor set
WARNING
The motor data parameters are critical to the correct operation of the soft starter's thermal model, and to the motor
overload protection. Always set Pr 1A to suit the motor's characteristics. The default settings of Pr 1B, 1C and 1D are
suitable for most applications. Consult the motor datasheet before changing these settings.
No
Function
Range
Default
1A
Motor Full Load Current
Model dependent
Model dependent
Matches the starter to the connected motor's full load current. Set to the full load current (FLC) rating shown on the motor
nameplate.
No
Function
Range
Default
1B
Locked Rotor Current
400 to 1200% FLC
600%
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the motor datasheet.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Digistart IS1x0043B series and is the answer not in the manual?

Emerson Digistart IS1x0043B series Specifications

General IconGeneral
BrandEmerson
ModelDigistart IS1x0043B series
CategoryController
LanguageEnglish

Related product manuals