58 Digistart IS User Guide
www.controltechniques.com Issue: 4
No
Function
Range
Default
5G
Reserved
N/A
N/A
This parameter is reserved for internal use.
No
Function
Range
Default
5H
Reserved
N/A
N/A
This parameter is reserved for internal use.
No
Function
Range
Default
5I
Frequency Check
Do Not Check, Start Only, Start/Run, Run
Only
Start/Run
Determines when and if the starter will monitor for a frequency trip.
No
Function
Range
Default
5J
Frequency Variation
±2, ±5, ±10, ±15 Hz
±5 Hz
Selects the soft starter's tolerance for frequency variation.
CAUTION
Running a motor outside its specified frequency for long periods can cause damage and premature failure.
No
Function
Range
Default
5K
Ground Fault Level
20mA, 30mA, 50mA, 75mA, 100mA, 150mA,
200mA, 300mA, 500mA, 750mA, 1A, 1.5A,
2A, 3A, 5A, 7.5A, 10A, 15A, 20A, 30A, 50A
100mA
Sets the trip point for ground fault protection.
The Digistart IS can be configured to trip if ground fault exceeds a specified level while the motor is running. Ground fault is a
dynamic trip based on phase current measurements every half-cycle.
NOTE
Ground fault protection is only available if the RTD/PT100 and ground fault protection card is fitted.
No
Function
Range
Default
5L
Motor Temperature Check
Do Not Check, Check
Do Not Check
Selects whether the Digistart IS will verify the motor has sufficient thermal capacity for a successful start. The soft starter compares
the motor's calculated temperature with the temperature rise from the last motor start and only operates if the motor is cool enough
to start successfully.
8.8.7 Group 6 - Protection delays
Protection delays slows the Digistart IS's response to the trip condition, avoiding trips due to momentary fluctuations.
No
Function
Range
Default
6A
Current Imbalance Delay
00:00 to 04:00 (minutes:seconds)
00:03
6B
Underpower Delay
00:00 to 04:00 (minutes:seconds)
00:05
6C
Overpower Delay
00:00 to 01:00 (minutes:seconds)
00:00
6D
Reserved
-
-
6E
Reserved
-
-
6F
Frequency Delay
00:00 to 04:00 (minutes:seconds)
00:01
No
Function
Range
Default
6G
Restart Delay
00:01 to 60:00 (minutes:seconds)
00:10
The Digistart IS can be configured to force a delay between the end of a stop and the beginning of the next start. During the restart
delay period, the display shows the time remaining before another start can be attempted.
No
Function
Range
Default
6H
Ground Fault Delay
00:01 to 04:00 (minutes:seconds)
00:03
NOTE
Ground fault protection is only available if the RTD/PT100 and ground fault protection card is fitted.