Quick Start
Commissioning
58 Digistart IS User Guide
www.controltechniques.com Issue: 4
This parameter is reserved for internal use.
This parameter is reserved for internal use.
Do Not Check, Start Only, Start/Run, Run
Only
Determines when and if the starter will monitor for a frequency trip.
Selects the soft starter's tolerance for frequency variation.
Running a motor outside its specified frequency for long periods can cause damage and premature failure.
20mA, 30mA, 50mA, 75mA, 100mA, 150mA,
200mA, 300mA, 500mA, 750mA, 1A, 1.5A,
2A, 3A, 5A, 7.5A, 10A, 15A, 20A, 30A, 50A
Sets the trip point for ground fault protection.
The Digistart IS can be configured to trip if ground fault exceeds a specified level while the motor is running. Ground fault is a
dynamic trip based on phase current measurements every half-cycle.
Ground fault protection is only available if the RTD/PT100 and ground fault protection card is fitted.
Selects whether the Digistart IS will verify the motor has sufficient thermal capacity for a successful start. The soft starter compares
the motor's calculated temperature with the temperature rise from the last motor start and only operates if the motor is cool enough
to start successfully.
8.8.7 Group 6 - Protection delays
Protection delays slows the Digistart IS's response to the trip condition, avoiding trips due to momentary fluctuations.
00:00 to 04:00 (minutes:seconds)
00:00 to 04:00 (minutes:seconds)
00:00 to 01:00 (minutes:seconds)
00:00 to 04:00 (minutes:seconds)
00:01 to 60:00 (minutes:seconds)
The Digistart IS can be configured to force a delay between the end of a stop and the beginning of the next start. During the restart
delay period, the display shows the time remaining before another start can be attempted.
00:01 to 04:00 (minutes:seconds)
Ground fault protection is only available if the RTD/PT100 and ground fault protection card is fitted.