1592001830 XC645D GB r3.4 04.09.2017.docx XC645D 33/50
Regulation according to the running hours
The algorithm switch on and off the loads according to the running hours of each load. In this way
the running hours are balanced.
Example
4 Fans: oA2 =FAn; oA3 = FAn; oA4 = FAn; oA6 = FAn:
rot = yES rotation enabled