1592001830 XC645D GB r3.4 04.09.2017.docx XC645D 43/50
Code
Description
Cause
Action
Reset
P1
P1 probe
failure alarm
Probe failure or
out of range
The
compressors
are activated
according to
the SPr or
PoPr
parameters.
Automatically as soon as the probe restarts working.
P2
P2 probe
failure alarm
Probe failure or
out of range
The fans are
activated
according to
the FPr
parameters.
Automatically as soon as the probe restarts working.
P3
P3 probe
failure alarm
Probe 3 failure
or out of range
The functions
related to the
third probe
are disabled.
Automatically as soon as the probe restarts working.
P4
P4 probe
failure alarm
Probe 4 failure
or out of range
The functions
related to the
fourth probe
are disabled.
Automatically as soon as the probe restarts working.
EA1
EA2
EA3
EA4
Load safeties
alarm
Safeties
compressor/fan
input activation.
NOTE: with step
compressors 1
input for each
compressor has
to be used.
the
correspondin
g load is
turned off.
(with step
compressors
all relays
referred to
the input are
disabled).
Recovery depends on ALMr parameter:
With ALMr = no The instrument restart the standard
operating mode when the input is disabled.
With ALMr = yES manual recover for the alarms of
compressors and fans. Push the DOWN key for 3s.
C1-LA
Minimum
pressure
(temperature)
alarm
compressors
section
Suction pressure
or temperature
lower than
LAL value
signaling only
Automatically: as soon as the pressure or
temperature reaches the (LAL+ differential) value.
(differential = 0.3bar or 1°C)
F-LA
Minimum
pressure
(temperature)
alarm fans
section
Condensing
pressure or
temperature
lower than
LAF value
signaling only
Automatically: as soon as the pressure or
temperature reaches the (LAF+ differential) value.
(differential = 0.3bar or 1°C)
C1-HA
Maximum
pressure
(temperature)
alarm
compressors
section
Suction pressure
or temperature
higher than
HAL value
signaling only
Automatically: as soon as the pressure or
temperature reaches the (HAL - differential) value.
(differential = 0.3bar or 1°C)
F-HA
Maximum
pressure
(temperature)
alarm fans
section
Condensing
pressure or
temperature
higher than
HAF value
Depends on the
parameter HFC
Automatically: as soon as the pressure or
temperature reaches the (HAF - differential) value.
(differential = 0.3bar or 1°C)