D
Daniel DixonSep 2, 2025
What are the possible causes of motor overload in Emerson EV2000-4T0055G/0075P DC Drives?
- AAnne HarrisSep 2, 2025
If your Emerson DC Drives indicate a motor overload, it could be due to an improper V/F curve; set the V/F curve and torque boost value correctly. Check the AC supply voltage, as low voltage can cause this. If a common motor has operated with a heavy load at low speed for a long time, use a special motor designed for continuous operation. Also, the motor’s overload protection threshold might be improper, so modify it. Finally, check the load, as fast load changes can contribute to this issue.