Static, dynamic & 
recovery limits 
Check & 
corrective action 
Compressor phase 
current foldback timeout 
If compressor is running 
outside the envelope for 
30 seconds. 
In Active Envelope 
protection mode the 
compressor is allowed to 
run outside for a longer 
time. 
Check if the compressor is running within the 
envelope. Check the envelopes in Appendix 4 
and read chapter 4.4 for further information on 
Envelope Control. 
Module temperature 
foldback timeout 
Speed-drop protection 
limit / recovery value 
EV3150B, EV3185B: 
108 °C / 103 °C 
Check if the fan is on and working properly. If 
the fan is broken, the module will overheat, and 
the drive will report this fault. 
Input current foldback 
timeout 
Speed-drop protection 
limit / recovery value 
EV3150B: 30 A / 28 A 
EV3185B: 41 A / 39 A 
Check the compressor load. This fault will be 
triggered if the load is too high for a certain 
speed during 30 seconds. 
This fault will be triggered if the fan stops 
working. If the fan has been replaced, check the 
connections as per instructions in chapter 7.2. 
If the fan still does not work, replace the drive. 
Drive module HW 
overcurrent 
This fault appears when there is a short 
between phases or in case of a locked rotor 
event. Check if the connections between drive 
and compressor are properly made and restart 
the drive. 
If the fault persists, replace the drive, as the 
power module might be damaged. 
Compressor U phase 
overcurrent / sensor fault 
If this fault appears, it can only be cleared with a 
power cycle on the drive. Check the wiring to 
the compressor and run the motor again. 
If the fault persists, replace the drive. 
Compressor V phase 
overcurrent / sensor fault 
Compressor W phase 
overcurrent / sensor fault 
EV3150B: 28 A RMS 
EV3185B: 39 A RMS 
Send a clear fault command then restart the 
compressor. Adjust the load so that the output 
current does not exceed 38 A for 18.5 kW and 
27 A for 15 kW. 
Compressor start-up fault 
This fault is triggered when the compressor fails 
to start 3 times. Check if the wires are correctly 
connected to the compressor. If it still fails, try 
interchanging two wires and restart the 
compressor. 
This fault will appear at start-up if the HPS is not 
connected. If it is not used, a short must be 
made on the HPS terminals. The fault can only 
be cleared with a power cycle. 
Compressor motor phase 
current imbalance 
The difference between the maximum and 
minimum compressor phase currents RMS 
value exceeds 4 A. Check the compressor 
U,V,W connections first, and make sure that the 
screws are tight. 
If the problem persists, check the values of the 
compressor currents with the scope. If a 
difference in currents can be observed on the 
scope, replace the drive first. If the fault 
persists, the compressor must be replaced. 
The maximum value of 
input voltage (RMS) 
exceeds 1.5 x the 
minimum value of input 
voltage 
Check the connection to the grid. This fault will 
be triggered when a phase is not properly 
connected. 
EV3150B: 31 A RMS 
EV3185B: 42 A RMS 
The compressor load is too high. Try reducing it 
and check if the fault still appears. 
ADC base AD > 2662 or 
ADC base AD < 1433 
Restart the drive. 
If the fault persists, replace the drive. 
Check that all motor U,V,W phases are properly 
connected and that there is no loose cable. This 
fault is triggered when one of the motor cables 
is not connected.