EasyManuals Logo

Emerson EV3150B User Manual

Emerson EV3150B
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
26 AGL_Sol_EV3_E_Rev_02
No
Alert &
fault message
Static, dynamic &
recovery limits
Protective action
Analog
board
Alarm code
#OneEmerson
Register bit
Check &
corrective action
14
Compressor phase
current foldback timeout
If compressor is running
outside the envelope for
30 seconds.
In Active Envelope
protection mode the
compressor is allowed to
run outside for a longer
time.
Compressor trip
E19
27
81.2
Check if the compressor is running within the
envelope. Check the envelopes in Appendix 4
and read chapter 4.4 for further information on
Envelope Control.
15
Module temperature
foldback timeout
Speed-drop protection
limit / recovery value
EV3150B, EV3185B:
108 °C / 103 °C
Compressor
speed drop
E20
28
81.3
Check if the fan is on and working properly. If
the fan is broken, the module will overheat, and
the drive will report this fault.
16
Input current foldback
timeout
Speed-drop protection
limit / recovery value
EV3150B: 30 A / 28 A
EV3185B: 41 A / 39 A
Compressor
speed drop
E21
29
81.4
Check the compressor load. This fault will be
triggered if the load is too high for a certain
speed during 30 seconds.
17
Cooling fan fault
-
Compressor trip
E64
31
85.15
This fault will be triggered if the fan stops
working. If the fan has been replaced, check the
connections as per instructions in chapter 7.2.
If the fan still does not work, replace the drive.
18
Drive module HW
overcurrent
Dependent on the system
Compressor trip
E44
49
84.11
This fault appears when there is a short
between phases or in case of a locked rotor
event. Check if the connections between drive
and compressor are properly made and restart
the drive.
If the fault persists, replace the drive, as the
power module might be damaged.
19
Compressor U phase
overcurrent / sensor fault
Read from EEPROM
Compressor trip
E41
50
84.8
If this fault appears, it can only be cleared with a
power cycle on the drive. Check the wiring to
the compressor and run the motor again.
If the fault persists, replace the drive.
20
Compressor V phase
overcurrent / sensor fault
Read from EEPROM
Compressor trip
E42
51
84.9
21
Compressor W phase
overcurrent / sensor fault
Read from EEPROM
Compressor trip
E43
52
84.10
22
Compressor overload
EV3150B: 28 A RMS
EV3185B: 39 A RMS
Compressor trip
E48
53
84.15
Send a clear fault command then restart the
compressor. Adjust the load so that the output
current does not exceed 38 A for 18.5 kW and
27 A for 15 kW.
23
Compressor start-up fault
-
Compressor trip
E14
57
80.13
This fault is triggered when the compressor fails
to start 3 times. Check if the wires are correctly
connected to the compressor. If it still fails, try
interchanging two wires and restart the
compressor.
24
High pressure protection
N/A
Compressor trip
E09
58
80.8
This fault will appear at start-up if the HPS is not
connected. If it is not used, a short must be
made on the HPS terminals. The fault can only
be cleared with a power cycle.
25
Compressor motor phase
current imbalance
-
Compressor trip
E07
59
82.0
The difference between the maximum and
minimum compressor phase currents RMS
value exceeds 4 A. Check the compressor
U,V,W connections first, and make sure that the
screws are tight.
If the problem persists, check the values of the
compressor currents with the scope. If a
difference in currents can be observed on the
scope, replace the drive first. If the fault
persists, the compressor must be replaced.
26
AC input loss of phase
The maximum value of
input voltage (RMS)
exceeds 1.5 x the
minimum value of input
voltage
Compressor trip
E10
60
80.9
Check the connection to the grid. This fault will
be triggered when a phase is not properly
connected.
27
AC input overcurrent
EV3150B: 31 A RMS
EV3185B: 42 A RMS
Compressor trip
E02
63
80.1
The compressor load is too high. Try reducing it
and check if the fault still appears.
28
ADC fault
ADC base AD > 2662 or
ADC base AD < 1433
Compressor trip
E56
68
85.7
Restart the drive.
If the fault persists, replace the drive.
29
Microelectronic fault
-
Compressor trip
E35
-
84.2
30
Compressor loss of phase
-
Compressor trip
E10
-
80.2
Check that all motor U,V,W phases are properly
connected and that there is no loose cable. This
fault is triggered when one of the motor cables
is not connected.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson EV3150B and is the answer not in the manual?

Emerson EV3150B Specifications

General IconGeneral
BrandEmerson
ModelEV3150B
CategoryDC Drives
LanguageEnglish

Related product manuals