Shutdown
To take the regulator out of operation:
  1.  If a bypass line is used, slowly open the  
bypass line block valve while monitoring the 
downstream pressure. 
  2. Close the control line shuto valve. 
  3. Close the downstream block valve. 
  4. Close the upstream block valve. 
  5.  If a pressure-loaded or on-o pilot is used, close 
the needle valve to the pilot. 
  6.  Vent the regulator and control line to release any 
trapped pressure.
Troubleshooting
Operating diculties may be experienced with this 
valve as a result of improper installation, improper 
valve sizing, damage to internal parts, trim wear or an 
accumulation of dirt, boiler compound or other foreign 
materials on internal parts. When trouble occurs, 
check the following:
Type 92B
Build-up of Downstream Pressure
  1. Check for plugged bleed tting (key 61, Figure 8).
  2.  Check the screen (key 77, Figure 9 or 10) for 
clogging and the other pilot internal parts for 
accumulation of dirt, boiler compound or  
other materials.
Failure to Maintain Downstream Pressure
  1. Check for ruptured diaphragm (key 60, Figure 8).
  2. Check to see that the valve is not undersized.
Cycling or Hunting
Check to see that the valve is not oversized. A cycling 
Type 92B might possibly control the downstream 
pressure within acceptable limits but the life of the 
diaphragms, guide bushings, seat ring and valve plug 
could be greatly reduced.
If cycling occurs, as a result of oversizing or other 
causes, it can frequently be minimized by reducing 
the gain of the Type 92B. This can be accomplished 
by installing a suitable reducing regulator such as 
a Type MR95H in the Type 92B pilot supply line. 
Adjust the pilot supply line regulator to reduce pilot 
supply pressure to about 30 psig / 2.1 bar above the 
outlet pressure setting of the Type 92B valve. This 
arrangement can minimize cycling and still provide 
adequate pilot supply pressure to ensure full opening 
of the main valve plug, if required.
Note
The 30 psig / 2.1 bar is suggested for 
units which include the standard 17-7 PH 
stainless steel main spring. This spring 
requires approximately 20 psig / 1.4 bar 
diaphragm dierential pressure to fully 
stroke the main valve. If the lighter rate 
Inconel
®
 spring is used, only about  
10 psig / 0.69 bar diaphragm dierential 
pressure is required to fully stroke the unit. 
Therefore, the pilot supply pressure can be 
reduced to about 20 psig / 1.4 bar above 
the outlet pressure setting of the control 
valve without loss of control capability.
Maintenance
CAUTION
Before disassembly or removing the 
control valve from the line, isolate it 
from the pressure system and release all 
the pressure from the control valve.
Due to normal wear, parts must be periodically 
inspected and replaced if necessary. The frequency of 
inspection depends on the severity of the service.
Main Valve Disassembly
Type 92B
Key numbers listed are shown on the body assembly 
drawing, Figure 8.
  1. Remove all tubing.
  2. Mark the outside edge of the body and diaphragm 
case anges with assembly marks to ensure proper 
assembly. Remove bolts from diaphragm case and 
lift o the case. On cast iron body sizes NPS 1-1/2 
through 4 / DN 40 to 100, rst remove the loading 
tubing compression coupling tting from the  
pipe nipple.
Inconel
®
 is a trademark owned by Special Metals Corporation.
9
Type 92B