Transducer Block
March 2006
5-51
Table 5-13. Transducer Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Description
Protect
Category
Initial ValueRangeMode
RO /
RW
Index
Number
INST_ALERTS_ACTIVE
74
Elect Active
ELECT_ACTIVE
74.1 RO
(1)
ALL
0: Drive Current
1: Drive Signal
2: Memory Failure
Pending
3: Static Memory
4: Processor
5: I/O Processor
6: Output Block Timeout
7: Block Set to Defaults
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Electronics Alert status
Sensor Active
SENSOR_ACTIVE
74.2 RO
(1)
ALL
0: Travel Sensor
1: Port A Pressure
Sensor
2: Port B Pressure
Sensor
3: Supply Pressure
Sensor
4: Temperature Sensor
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Sensor Alert status
Enviro Active
ENVIRO_ACTIVE
74.3 RO
(1)
ALL
0: Supply Pressure High
1: Supply Pressure Low
2: Temperature High
3: Temperature Low
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Enviro Alert status
Tvl Active
TRAVEL_ACTIVE
74.4 RO
(1)
ALL
0: Travel Deviation
1: Travel Limit High High
2: Travel Limit Low Low
3: Travel Limit High
4: Travel Limit Low
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Travel Alert status
Prox Active
PROX_ACTIVE
74.5 RO
(1)
N/A
0: Travel Open
1: Travel Closed
2: Proximity High High
3: Proximity High
4: Proximity Low
5: Proximity Low Low
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Proximity Alert status.
Tvl History Active
TVL_HISTORY_ACTIVE
74.6 RO
(1)
ALL
0: Cycle Counter
1: Travel Accumulator
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Travel History Alert status
Performance Active
PERF_ACTIVE
74.7 RO
(1)
ALL
0: Performance Critical
1: Performance
Reduced
2: Performance
Information
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Performance Diagnostic Alert
status
PD Event Active
PD_EVENT_ACTIVE
74.8 RO
(1)
ALL
0: High I/P Drive Signal
1: Low I/P Drive Signal
2: High Air Mass Flow
3: Large Travel
Deviation
4: Low Supply Pressure
5: High Supply Pressure
6: High Crossover
Pressure
7: Low Crossover
Pressure
8: High I/P Drive Signal
9: Low I/P Drive Signal
10: High Air Mass Flow
11: Large Travel
Deviation
12: Low Supply Pressure
13: High Supply
Pressure
14: High Crossover
Pressure
15: Low Crossover
Pressure
16: No Air Mass Flow
Estimate
All bits: 0 N/A
Data Type: Bit String
0=inactive
1=active
Performance Diagnostic event
status.
Continued
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher Fieldvue DVC6030f and is the answer not in the manual?

Emerson Fisher Fieldvue DVC6030f Specifications

General IconGeneral
BrandEmerson
ModelFisher Fieldvue DVC6030f
CategoryController
LanguageEnglish

Related product manuals