DVC6000f Series
March 2006
5-68
Figure 5-9. Analog Output Function Block Schematic
B2717 / IL
CAS   IN
Position
Feedback
Analog
Output
Access
Analog
Output
Access
Analog
Input
Shed
Mode
SP
HI/LO
Limit
SP
Rate
Limit
Convert
and Status
Calculation
BKCAL 
 OUT
OUT
RCAS 
 OUT
RCAS 
 IN
SP 
 RATE   DN
SP   RATE   UP
SP 
 WRK
PV 
 SCALE
IO 
 OPTS
Operator
Setpoint
READ 
 BACK
PV
SP 
 LOW   LIM
SP   HI   LIM
CHANNEL
MODE
limited SP [8] condition is reflected in the
BKCAL_OUT [25] status. When simulation is enabled
through the SIMULATE [10] attribute, you can set the
value and status for PV [7] and READBACK [16].
When the block is in Cas mode and the CAS_IN [17]
input goes bad, the block sheds mode to the next
permitted mode.
Setting the Output  
To set the output for the AO block, you must first set
the mode to define the manner in which the block
determines its setpoint. In Manual mode the value of
the output attribute (OUT [9]) must be set manually by
the user, and is independent of the setpoint. In
Automatic mode, OUT [9] is set automatically based
on the value specified by the set point (SP [8]) in
engineering units and the I/O Options attribute. In
addition, you can limit the SP [8] value and the rate at
which a change in the SP [8] is passed to OUT [9].
In Cascade mode, the cascade input connection
(CAS_IN [17]) is used to update the SP [8]. The back
calculation output (BKCAL_OUT [25]) is wired to the
back calculation input (BKCAL_IN [27]) of the
upstream block that provides CAS_IN [17]. This
provides bumpless transfer on mode changes and
windup protection in the upstream block.
Note
You must wire BKCAL_OUT [25] to
BKCAL_IN [27] of the upstream block
that provides CAS_IN [17]. Otherwise,
the AO the upstream block will not
initialize properly, and the setpoint at
CAS_IN [17] will not be passed to OUT
[9].
The OUT [9] attribute or an analog readback value,
such as valve position, is shown by the process value
(PV [7]) attribute in engineering units.
To support testing, you can enable simulation, which
allows you to manually set the channel feedback.
There is no alarm detection in the AO function block.
To select the manner of processing the SP and the
channel output value configure the setpoint limiting
5