DVC6000f Series
March 2006
5-18
Table 5-5. Resource Block Parameter Definitions (Continued)
Label
PARAMETER_NAME
Index
Number
RO /
RW
Mode Range
Initial
Value
Description
Factory Serial Number
FACTORY_SN
50 RO NA NA spaces
Data Type: Visible String
Instrument serial number set by manufacturing.
Field Serial Number
FIELD_SN
51 RW NA Any String spaces
Data Type: Visible String
Instrument serial number set in the field.
Detailed Status
DETAILED_STATUS
52 RO NA NA
Data Type: Uint32
Not used by the DVC6000f.
Time Since Reset
TIME_SINCE_RESET
53 RO NA NA 0
Number of seconds since the last time
DVC6000f was restarted. Restart due to power
up or restart command.
Device ID
DEVICE ID
54 RO NA NA Device ID
Data Type: Visible String
Unique 32 character ID used to identify the
device.
STBY_SOFTWARE_REV
55
STBY_SOFTWARE_REV_MAJOR 55.1 RO NA 0−255 *
Data Type: Uint8
Describes software revision information. This is
the revision of the alternative firmware.
*Initial value depends on revision of software in
stby.
STBY_SOFTWARE_REV_MINOR 55.2 RO NA 0−255 *
STBY_SOFTWARE_REV_BUILD 55.3 RO NA 0−255 *
STBY_IO_SOFTWARE_REV 55.4 RO NA 0−255 *
STBY_DIAG_CAL_REV 55.5 RO NA 0−255 *
STBY_SOFTWARE_REV_ALL 55.6 RO NA XX.XX.XX.XX.XX NA
Data Type: Visible String
Describes software revision information.
*Initial value depends on revision of software in
stby. The range of this parameter consists of
55.1 through 55.5 values, converted to text,
and linked together.
5