Chapter 7 - Appendix   
7.1 Specifications   
7.1.1 Electronic bypass   
The Electronic bypass package features a user friendly application specific 
keypad to simplify operation and provide status indication.     
Approvals:   
VFD Section – UL508C 
Bypass Section – UL508A 
 
Design:  3 contactor bypass 
NEMA 1 enclosure   
Electronic bypass keypad / annunciator panel   
32-bit Microprocessor     
Hand/Off/Auto pushbuttons   
Test/VFD/Bypass pushbuttons     
Auto transfer to bypass on fault (selectable)   
Damper Mode (programmable)   
Damper actuator control (5 Amps @ 125 Vac relay contact)   
Smoke / fire alarm – programmable to:
 
Purge mode   
Zero speed mode   
Four (4) relay outputs.   
Dry contact digital i
nputs  
 
Narrow footprint   
PID controller   
Class 20 motor overload relay   
One (1) analog output:   
0-10 Vdc, scalable   
Two (2) analog inputs – programmable for:   
0-10 Vdc, scalable   
4-20 mA, scalable (default auto speed input)   
Speed search function   
Digital manual speed control   
 
Operating conditions:   
Altitude: to 3,300 ft, higher with derating   
Ambient operating temp. +32
o
 to +104
o
F (0
o
 to +40
o
C)  
Storage temp .-40
o
 to +140
o
F (-40
o
 to +60
o
C)  
95% relative humidity, non-condensing.     
Input voltage +10%, -10%.    208, 230 and 460 Vac   
Protected from exposure to direct sunlight