EasyManua.ls Logo

Emerson Hydrastep 2468 series - 3 C.3 Opto-Isolated Output Board Configuration

Emerson Hydrastep 2468 series
186 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Opto-isolated Output Board Option Hydrastep 2468CB & 2468CD Manual
3c-6 24685034
3C.3 OPTO-ISOLATED OUTPUT BOARD CONFIGURATION
The 24680505 Opto-isolated Output Board has three configuration switches:
SW6: Selects Electrode or Alarm state for Opto-output 1.
SW1 - SW4: Selects individual electrode for opto-outputs I to 4.
SW5: Selects Opto-outputs 1 - 4 to be energised when electrodes in
steam or in water.
Figure 3c.1 provides a view of the output board layout to highlight the positions of the various
configuration switches.
Figure 3c.1 - View of opto-isolated board showing switch positions and output pin details