22
11: Programmable output Shutdown Time setting
NoteThis function is not supported by the Rack model with parallel function.
Interface
Setting
Parameter 2: Set shutdown time for programmable output.
Setting range is from 0 to 300. When shutdown time arrives, the
programmable output/terminal will be cut off. The default value is
30 minutes.
3-8. Operating Mode/Status Description
Operating
mode/status
Description
LCD display
AC mode
When the input voltage is within acceptable
range, UPS will provide pure and stable AC
power to output. The UPS will also charge
the battery at AC mode.
ECO mode
When the input voltage is within voltage
regulation range and ECO mode is enabled,
UPS will bypass voltage to output for energy
saving.
CVCF mode
When input frequency is between 46Hz and
64Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The UPS
will still charge battery under this mode.
Battery mode
When the input voltage is beyond the
acceptable range or power failure, UPS will
backup power from battery and alarm will
beep every 4 seconds.