24
3-10. Warning Indicator
If more than one warning situation occurs, it will display warning codes one by one.
Warning Description
code
Icon (flashing)
Alarm
Battery is not connected
01
Beeping every second
Over charge
07
Beeping every second
Low battery
08
Beeping every second
Overload
09
Beeping twice every second
Fan failure
0A
Beeping every second
EPO enabled
0B
Beeping every second
Over temperature
0D
Beeping every second
Charger failure
0E
Beeping every second
I/P fuse broken
10
Beeping every second
Overload 3 times in 30
minutes
33
Beeping every second
Cover of maintain switch is
open
3A
Beeping every second
Parallel protection is
activated.
3F
Beeping every second

Related product manuals