EasyManua.ls Logo

Emerson Liebert GXT4-6000RT230 - Page 24

Emerson Liebert GXT4-6000RT230
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Chapter 5 Installation and Configuration
Note
1. The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of
the UPS or have appropriate an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.
2. The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local
codes. Output circuits must not share a common conduit with any other wiring.
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual

Table of Contents

Related product manuals