36 Chapter 11 Specifications
Chapter 11 Specifications
Table 11-1 UPS specifications
Parameters
GXT4-5000RT230E
4000W/5000VA
GXT4-6000RT230E
4800W/6000VA
GXT4-10000RT230E
9000W/10000VA
Dimensions, Rack Mount, W x D x H
430 × 574 × 217 (16.9 × 22.4 × 8.5)
430 × 581 × 261 (16.9 × 22.9 × 10.3)
516 × 745 × 530 (20.3 × 29.3 × 20.9)
530 × 745 × 563 (20.9 × 29.3 × 22.2)
Frequency
50Hz or 60Hz (Factory Default is 50Hz)
User Configurable VAC
(May be modified using included configuration program)
Without Battery Operation
176Vac ~ 280Vac
Input Frequency w/o Battery
Operation
40Hz ~ 70Hz
Input Power Connection
PD2-CE6HDWRMBS Standard
(See 3.2 Removable Power Distribution Box)
(See 3.3 Removable Power
Distribution Box)
Output Connections
PD2-CE6HDWRMBS Standard
(See 3.2 Removable Power Distribution Box)
(See 3.2 Removable Power
Distribution Box)
>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute
Valve-regulated, non-spillable, lead acid
Battery Mfr. / Part # 5AH battery, CSB HR1221W or YUASA NPH5-12
or Panasonic UP-RW1245
Batteries)
3 hr. to 90% capacity after full discharge into 100% load
If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass Operation
If input voltage returns to within ±10% of nominal output voltage
When the input frequency prevents synchronous operation
0 to 40 (32 to 104)see Table 11-2
0% to 95%, non-condensing
Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise less than <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual