EasyManua.ls Logo

Emerson Liebert NX 400V - Table 38 Bypass Input

Emerson Liebert NX 400V
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications
119
Table 39 Bypass input
Rated Power, kVA
Unit of
Measurement 30 40 60 80 100 120 140 160 200
Rated AC Voltage
1
V (ac)
380/400/415 V
three-phase four-wire, sharing neutral with the rectifier input and
providing neutral reference to the output
Rated current
380V
A 45 61 91 121 151 182 212 242 303
400V
43 58 87 116 145 174 202 230 288
415V
42 56 83 111 139 167 194 222 278
Overload capacity %
135% long term
170% 10 min
1000% 100 ms
125% long term
150% 10 min
1000% 100 ms
Upstream protection, bypass
line (by others)
Thermomagnetic circuit-breaker, rated up to 125% of nominal output
current. IEC 60947-2 curve C.
Current rating of neutral cable A 1.7 In 1.52In 1.35In
Frequency
2
Hz 50 / 60
Transfer time (between
Bypass and Inverter)
ms
Synchronous transfer:
1ms
Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)
or 40, 60, 80, 100 ms selectable
Bypass voltage tolerance % V (ac)
Upper limit: +10, +15 or +20, default +15
Lower limit –10, -20, -30 or -40, default: -20
(delay time to accept steady bypass voltage: 10 sec)
Bypass frequency tolerance % ± 2.5, ±5, ±10 or ±20 default ±10
Synchronisation - Window Hz Rated frequency ±2 Hz (selectable ± 0.5 to ± 3Hz)
1. Factory set to 400V – 380 or 415V selectable by commissioning engineer.
2. Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter.

Table of Contents

Related product manuals