14 PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide GFK-2941K
• WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
• WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS AREAS, TURN
OFF POWER BEFORE REPLACING OR WIRING MODULES.
ATEX Zone 2
This module must be mounted in an enclosure certified in accordance with
EN60079-15 for use in Zone 2, Group IIC and rated IP54. The enclosure shall
only be able to be opened with the use of a tool.
Grounding
The RX3i rack into which this product will be mounted must be grounded
per the instructions provided in PACSystems RX3i System Manual, GFK-2314.
Also, if an Energy Pack (IC695ACC402) is connected, its ground-strap must
be grounded as described in PACSystems RX3i Energy Pack IC695ACC402
Quick Start Guide, GFK-2939.