16 PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide GFK-2941K
Basic Installation Steps
For startup and configuration of the CPE330, complete the following steps.
For full details on CPE330 operation, refer to the PACSystems RX3i & RSTi-EP
CPU Reference Manual, GFK-2222 or later.
1. Turn power off at the RX3i rack and install the CPE330 in a double-
slot which is CPU-compatible (refer to PACSystems RX3i System
Manual, GFK-2314 Chapter 3). Typically, the CPU is in the left-most
slot pair, or in the pair of slots to the right of the power supply
module.
2. If used, mount the compatible RX3i Energy Pack (IC695ACC402)
within 3 feet of the CPU. The dedicated interconnect cable attaches
to the underside of CPE330. Follow interconnect and grounding
instructions in PACSystems RX3i Energy Pack IC695ACC402 Quick Start
Guide, GFK-2939. Secure the two retention flat-head screws with a
very small slotted screwdriver.
3. Set the pair of hook tabs at top rear of the CPU module into two
adjacent notches on the alignment rail of the RX3i rack backplane.
This aligns the module with the intended slots in the main rack and
with the right-side connector of this pair.
4. Swing the module down until the rear connector on the CPU module
engages the mating backplane connector. Firmly engage the
connectors.
5. Visually inspect the module to be sure it is properly seated.