17 PACSystems™ RX3i 64 MB CPU w/Ethernet Quick Start Guide GFK-2941K
6. Using a Phillips head screwdriver, secure the two captive M3 x 5 mm
machine screws into the matching threaded holes in the backplate
of the RX3i I/O rack. The two screws are located at the bottom rear
of the CPU module. Tighten.
7. Apply power to the rack.
Note: When the ACC402 Energy Pack is powered up, a period of time is
required to charge it up to its operating level. During this time, the
Energy Pack will indicate this condition via its LEDs (refer to
PACSystems RX3i Energy Pack IC695ACC402 Quick Start Guide, GFK-
2939).
The CPE330 will begin its boot cycle once ACC402 is charged. This
typically takes 90 seconds or less. In the event the ACC402 is faulty or
is not communicating, CPE330 commences operation without the
Energy Pack.
Redundancy Configuration
PAC Machine Edition 8.60 SIM 8 or later may be used to create native
CPE330 redundant applications when a rack-mounted IC695PNC001 is used
as the PROFINET Controller. If using the CPE330 Embedded PROFINET
Controller, use PME 9.50 SIM 7 or later.