RX3i PNC001 release 2.11 (or
later)
Hot Standby Redundancy
with PROFINET I/O
CRU320 Release 8.40
CPE330 Release 8.70
(Other CPU models are not supported)
RX3i PNC001 Release 2.00
Hot Standby Redundancy
with PROFINET I/O
CRU320 Release 8.00
CPE330 Release 8.70
(Other CPU models are not supported)
RX3i PNC001 Release 2.00
Non Hot Standby
Redundancy system
CPU320/CPU315 Release 7.13
CPE310/CPE305 Release 7.10
CRU320 Release 8.00
CPE302 Release 9.40
(Other CPU models are not supported)
PROFINET Controller
version requirements
Applications using the
IC695CPE302, CPE305,
CPE310, or CPE330
Version 10.05 (or later) with a
PNC001-Bxxx must also
upgrade the PNC to
Version 3.16 (or later) for
compatibility with the CPE3xx
controller.
If using PROFINET System
Redundancy, users MUST
upgrade the PNC001
(PROFINET Controller) to
Version 2.2 or later firmware.
Effective with PME 8.6 SIM 3 and PME 8.5 SIM 11 (PPS 2.6 SIM3
and PPS 2.5 SIM11), the PNC001 is configured to use RT Class 2
for redundant PROFINET connections. To meet specification, this
requires PNC001 firmware 2.2 or later. Under these conditions,
redundant VersaMax and/or CEP PROFINET I/O will NOT connect
or transfer I/O or Alarm Data if the PNC001 is running firmware
prior to Version 2.2.
RX3i PROFINET
Scanner Version
Requirements
RX3i PNC001 Release 3.00
New HW/FW to address
component obsolescence
IC695PNS001 with firmware version 3.00 or later and GSDML
version: GSDML-V2.3-GEIP-RX3iPNS-20170109.xml.
RX3i PNC001 Release 2.26
Support Remote Get Device
Information COMMREQ
IC695PNS001 with firmware version 2.41 or later and GSDML
version: GSDML-V2.3-GEIP-RX3iPNS-20160602.xml.
Programmer version
requirements
PME 8.50 SIM 9 or 8.60 SIM 1