GFK-2573Z Sep 2020
12
Subject
Feature
Minimum Version Required
RX3i PNC001 Release 2.11(or
later)
128 PROFINET Device
Support
4
Critical Network Port
4
PME 8.50 SIM 9 or 8.60 SIM 1
RX3i PNC001 Release 2.00 (or
later)
Hot Standby Redundancy
with PROFINET I/O
Non Hot Standby
Redundancy system using
CRU320
PAC Machine Edition 8.00 SIM 5
RX3i PNC001 Release 2.00 (or
later)
Non Hot Standby
Redundancy system
PAC Machine Edition 7.00 SIM 8
PNC001-Bxxx and PNC001-Ax Hardware Comparison
This section outlines differences between the new (-Bxxx) and old (-Ax) hardware implementations. Functionally, the
two are equivalent, except for the removal of the micro USB port and the Command Language Interface (CLI) which
operated via that port.
Topic
-Ax
-Bxxx
Appearance
Refer to Figure 2, GFK-2571K
Refer to Figure 3, GFK-2571K
Case
Plastic
Metal
Attachment to Rack
Via plastic case latch and heatsink screw
Via two Phillip’s head machine screws
Heatsink
Remove plastic knockout from rack
No knockout removal required
Status LEDs
6 LEDs
5 LEDs (no USB LED)
LED Behavior
Refer to Section 2.8, GFK-2571K
Refer to Section 2.8, GFK-2571K
Ethernet Port LEDs
4 singleton LEDs (top of faceplate)
4 banks of LEDs (bottom of faceplate).
The digits representing the port numbers
are backlit by LEDs.
µUSB Port
Present
Absent
Command Line
Interface
Uses µUSB Port
Not available
RJ45 Connector on
Faceplate
Absent
Present (Disabled)
Power Requirements
Higher
Lower
Operating Temperature
Range
0°C to 60°C
-25°C to 60°C
Module Reset
Pushbutton “Restart”
Membrane “Reset”
4
Attempts to store a configuration utilizing this feature to a prior-release PNC001 will result in an Unable to deliver configuration to module fault, which
leaves the PNC001 in an un-configured state.