2. Connect the leads as shown in Figure 5-1.
3. Tighten the terminal screws to ensure full contact with the terminal
block screw and washer. When using a direct wiring method, wrap
wire clockwise to ensure it is in place when tightening the terminal
block screw.
Note
The use of a pin or ferrule wire terminal is not recommended as the
connection may be more susceptible to loosening over time or under
vibration.
4. Ground housing to fulfill local grounding regulations.
5. Ensure proper grounding. It is important that the instrument cable
shield:
• Be trimmed close and insulated from touching the transmitter
housing
• Be connected to the next shield if cable is routed through a
junction box
• Be connected to a good earth ground at the power supply end
6. If transient protection is needed, refer to Grounding for transient
terminal block section for grounding instructions.
7. Plug and seal unused conduit connections.
8. Replace the housing cover.
May 2019 Quick Start Guide
Quick Start Guide 11