Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
13
STEP 5: VERIFY CONFIGURATION
Use any HART-compliant master to communicate with and verify
configuration of the 3051S. For the HART Diagnostics transmitter
(option code DA1), DD revision 3051S HDT Dev. 1 Rev. 1 is required.
A check () indicates the basic configuration parameters. At a
minimum, these parameters should be verified as part of the
configuration and startup procedure.
Table 1. HART Fast Key Sequence
Function Fast Key Sequence
Alarm Level Configuration 1, 4, 2, 7, 7
Alarm and Saturation Levels 1, 4, 2, 7
Analog Output Alarm Direction 1, 4, 2, 7, 6
Analog Output Trim 1, 2, 3, 2
Burst Mode On/Off 1, 4, 3, 3, 3
Burst Options 1, 4, 3, 3, 4
Damping 1, 3, 6
Date 1, 3, 4, 1
Descriptor 1, 3, 4, 2
Digital To Analog Trim (4-20 mA
Output)
1, 2, 3, 2, 1
Field Device Information 1, 4, 4, 1
LCD Display Configuration 1, 3, 7
Loop Test 1, 2, 2
Lower Sensor Trim 1, 2, 3, 3, 2
Message 1, 3, 4, 3
Number of Requested Preambles 1, 4, 3, 3, 2
Pressure Alert Configuration 1, 4, 3, 5, 3
Poll Address 1, 4, 3, 3, 1
Poll a Multidropped Transmitter Left Arrow, 3, 1, 1
Remapping 1, 4, 3, 6
Rerange- Keypad Input 1, 2, 3, 1, 1
Continued on Next Page