Quick Installation Guide
00825-0100-4801, Rev HA
February 2008
Rosemount 3051S
20
Setting the alarm values and direction is dependent on whether or not
the hardware switch option is installed. You can use a HART master or
communicator to set the Alarm and Saturation values.
Switches installed
1. If using a communicator, use the following fast key sequence to set
the Alarm and Saturation values.
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
2. Manually set the direction for the Alarm to HI or LO using the
ALARM switch as shown in Figure 2 on page 6.
Switches not installed
If using a communicator, use the following fast key sequence to set the
Alarm and Saturation values and the Alarm Direction:
Alarm Levels - Fast Key; 1, 4, 2, 7, 7
Saturation Levels - Fast Key; 1, 4, 2, 7, 8
Alarm Direction Fast Key; 1, 4, 2, 7, 6
4801_QIG_RevHA.fm Page 20 Tuesday, February 26, 2008 12:17 PM