ER5000 —
166
The ERTune™ Program: Basic Features
Delta
Initiates a step setpoint change by the value entered in the Delta
Amount entry eld. The value entered in the Delta Amount entry eld
can be positive or negative.
The Delta command can be used together with the Loop
command as a programming shortcut to move the setpoint to a
target level through a series of smaller setpoint step changes.
In the Prole below, segments 3 through 5 combine to increase
pressure from 50 psig to 70 psig over four loops and segments 6
through 8 return the pressure to 50 psig over four loops.
Change Variable
Sets the value of an internal variable of the ER5000, selected
from the Variable drop-down list, to the value entered in the Value
entry eld.
Refer to the Internal Variables section for a table listing all of the
ER5000’s internal variables, as well as detailed information about
the settings for the most commonly used variables.