Unidrive M200/201 Control Quick Start Guide 15
Issue Number: 2
Figure 4-13 Pr 00.005 = E.Pot (50 Hz)
Figure 4-14 Pr 00.005 = E.Pot (60 Hz)
When Pr 00.005 is set to E.Pot, the following
parameters may need to be adjusted:
• Motorized pot up/down rate (s/100 %)
• Motorized pot bipolar select (0 = unipolar, 1 =
bipolar)
• Motorized pot mode: 0 = zero at power-up, 1 = last
value at power-up, 2 = zero at power-up and only
change when the drive is running,
3 = last value at power-up and only change when
drive is running, 4 = zero at power-up and drive
disabled, only change when the drive is running.
1
2
4
0V
Voltage speed reference
input (AI 1)
DOWN
5
+ 10 V output
7
9
10
Digital output
(zero frequency)
Drive enable
11
12
13
14
Run reverse
Run forward
Analog output 1
(motor frequency)
UP
+ 24 V output
When Pr 00.005 is set to E.Pot, the following
parameters may need to be adjusted:
• Motorized pot up/down rate (s/100 %)
• Motorized pot bipolar select
(0 = unipolar, 1 = bipolar)
• Motorized pot mode: 0 = zero at power-up, 1 = last
value at power-up, 2 = zero at power-up and only
change when the drive is running,
3 = last value at power-up and only change when
drive is running, 4 = zero at power-up and drive
disabled, only change when the drive is running.
1
2
4
0V
Voltage speed reference
input (AI 1)
DOWN
5
+ 10 V output
7
9
10
Digital output
(zero frequency)
Not stop
11
12
13
14
Jog forward
Run
Analog output 1
(motor frequency)
UP
+ 24 V output
Unidrive M200_201 Control Quick Start Guide English Iss1.book Page 15 Wednesday, September 16, 2015 10:31 AM