Electronic Bypass Controller Installation and Commissioning Guide 9
2.4 Mounting & Clearances
Install the electronic bypass package on a vertical surface and allow the following
minimum clearances for normal heat dissipation.
Industrial Automation
TM
WARNING
WARNING
Potentially hazardous voltage
can exist within this device. Only fully trained, qualified personnel should
service this equipment.
Pressing the stop button will not remove power from this equipment.
Never service this equipment without first being sure all power is safely
removed. Hazardous voltage levels may exist for up to 5 minutes after
power is disconnected!
Industrial Automation
TM
WARNING
WARNING
Potentially hazardous voltage
can exist within this device. Only fully trained, qualified personnel should
service this equipment.
Pressing the stop button will not remove power from this equipment.
Never service this equipment without first being sure all power is safely
removed. Hazardous voltage levels may exist for up to 5 minutes after
power is disconnected!
12 in
6 in 12 in 6 in
TOP SIDE-TO-SIDE
Air Flow
Notes:
Ambient operating temperature; 32 °F to 104 °F (0 °C to 40 °C)
Install the unit in a dry environment free from oil mist and dust
Install the unit in a location free from radioactive materials, combustible materials,
harmful gases or liquids
Do not install the unit in a location susceptible to excessive vibrations
Do not install in direct sunlight
During installation, protect the unit from foreign particles such as metal shavings
produced by drilling
Failure to follow these notes could void the warranty