40 SI-Ethernet User Guide
Issue: 1
See Serial Number LS (S.00.004)
This parameter displays the current status of the module. All possible values are shown
in the table below.
When set, the module performs a warm reset. When the reset has been performed and
the module is performing it’s initialization routines the parameter will be cleared to zero.
S.00.005 Serial Number MS
Minimum 0 Maximum 99999999
Default Units
Type 32 Bit Volatile Update Rate Power-up write
Display Format None Decimal Places 0
Coding RO, ND, NC, PT
S.00.006 Status
Minimum -2 Maximum 3
Default Units
Type 8 Bit Volatile Update Rate Background
Display Format None Decimal Places 0
Coding RO, TE, ND, NC, PT
Value Text Description
-2 Bootldr-Update The bootloader is performing a flash update.
-1 Bootldr-Idle The bootloader is idle.
0 Initialising Module is currently initializing.
1 OK Module has initialized and has found no errors.
2 Config A configuration error has been detected.
3Error
An error has occurred preventing the module from
running correctly.
S.00.007 Reset
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate
Read every 200 ms,
Written to 0 on module
initialization.
Display Format None Decimal Places 0
Coding RW, NC
The drive, and any other modules fitted to the drive, will not be affected by the reset.