66 SI-Ethernet User Guide
Issue: 1
Defines the action to be taken for a timeout on the Rx1 link.
This parameter defines the slot in which an event will occur if a cyclic data timeout
occurs on the Rx1 link.
S.10.046 Rx1 Timeout Action
Minimum 0 Maximum 2
Default 0 Units
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 Trip Trip drive with Slx.Er and sub-trip code 106 (Cyclic Timeout)
1 Clear output PLC output parameters will have their values set to zero
2 Hold last Hold the last value in output parameters
S.10.047 Rx1 Timeout Event Destination
Minimum 0 Maximum 4
Default 0 Units
Type 8 Bit User save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 This slot Trigger module event in this slot
1 Slot 1 Trigger module event in slot 1
2 Slot 2 Trigger module event in slot 2
3 Slot 3 Trigger module event in slot 3
4 Slot 4 Trigger module event in slot 4
This feature is not yet implemented.
S.10.048 Rx1 Timeout Event Type
Minimum 0 Maximum 4
Default 0 Units
Type 8 Bit User save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, TE, BU
NOTE