SI-Ethernet User Guide 67
Issue: 1
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started Parameters
Key features
and Protocols
PC Applications Security Diagnostics
Glossary of
terms
Index
Defines the event to trigger in the given destination, as specified in Rx1 Timeout Event
Destination (S.10.047), if a cyclic data timeout occurs on the Rx1 link.
Value Text Description
0 No Event No event
1 Event Trigger module event
2 Event 1 Trigger module event 1
3 Event 2 Trigger module event 2
4 Event 3 Trigger module event 3
This feature is not yet implemented.
S.10.049 Rx1 Link Status
Minimum -30 Maximum 2
Default 0 Units
Type 8 Bit Volatile Update Rate Write on reset
Display Format None Decimal Places 0
Coding RO, TE
Value Text Description
-30 VLAN disabled
VLAN is required in order to guarantee timing in
synchronous mode but it is disabled
-29 Reserved 29 Reserved for future use
-28 Reserved 28 Reserved for future use
-27 Reserved 27 Reserved for future use
-26 Reserved 26 Reserved for future use
-25 Reserved 25 Reserved for future use
-24 Reserved 24 Reserved for future use
-23 Reserved 23 Reserved for future use
-22 Invalid DST IP Destination IP address is invalid
-21 SYNC unsupported
Sync link does not support mappings to other option
parameters
-20 MEC offset Incorrect MEC offset
-19 Invalid tx rate Tx rate must be a factor of 1 second
-18 Too many mapping
The number of mapping items exceeds the range
supported
-17 Link busy The link specified is busy
-16 Invalid profile The profile is invalid
-15 Invalid mapping The mapped parameter does not exist
-14 Read only param The mapped parameter is read only