EasyManuals Logo

Emerson Wireless 1410 Gateway User Manual

Emerson Wireless 1410 Gateway
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
Figure 3-5: Emerson Smart Wireless Gateway 1410 Terminal Block
+
- A+ B-
S
Power
Reset
A
B C
A
5-screw terminal block
B
24 VDC (nominal) power input
C
Serial Modbus
®
Ethernet connections should use Cat5e shielded cable to connect to an Ethernet hub,
switch, or router. The maximum cable length should not exceed 328-ft. (100 m).
3.4.3
RS-485
The Gateway can be ordered with an optional RS-485 (serial) connection (Figure 3-6).
Modbus terminals are labeled A and B on the wiring diagram. This connection is used to
communicate Modbus RTU on an RS-485 data bus.
Use 18 AWG single twisted shielded pair wiring to connect the Gateway to the RS-485 data
bus. The total bus length should not exceed 4000-ft. (1220 m). Connect the Tx - (negative,
receive) wire to terminal A and the Rx + (positive, transmit) wire to terminal B. The wiring
shield should be trimmed close and insulated from touching the Gateway enclosure or
other terminations.
If the existing data bus uses a 4-wire Full Duplex configuration, see Figure 3-6 to convert to
a 2-wire Half Duplex configuration.
Installation Reference Manual
September 2020 00809-0200-4410
22 Emerson.com/Rosemount

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Wireless 1410 Gateway and is the answer not in the manual?

Emerson Wireless 1410 Gateway Specifications

General IconGeneral
BrandEmerson
ModelWireless 1410 Gateway
CategoryGateway
LanguageEnglish

Related product manuals