Table 5-3: System Settings Protocols Ethernet/IP (continued)
Terms Description
NaN Not a number is reported if the value’s associated status indicates a
critical failure.
+Inf Positive infinity is reported if the value’s associated status indicates a
critical failure.
-Inf Negative infinity is reported if the value’s associated status indicates a
critical failure.
Other User defined value is reported if the value’s associated status indicates
a critical failure.
Value reported for error
(native integer)
User defined value is reported if the value’s associated status indicates
a critical failure. Only used if the Gateway is using integer
representation.
Unmapped parameter
read response
This is the value returned by the Gateway if the EtherNet/IP master
requests a register with no data assigned to it (empty register). It is
recommended this be set to zero fill to prevent errors.
Parameter mapping Register Mapping is the process of assigning data points from wireless
field devices to EtherNet/IP registers. These registers can then be read
by a EtherNet/IP master or client. EtherNet/IP register mapping can be
found by navigating to System Settings Protocols Ethernet/IP.
Operation and Maintenance Reference Manual
September 2020 00809-0200-4410
42 Emerson.com/Rosemount

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Wireless 1410 Gateway and is the answer not in the manual?

Emerson Wireless 1410 Gateway Specifications

General IconGeneral
BrandEmerson
ModelWireless 1410 Gateway
CategoryGateway
LanguageEnglish

Related product manuals