FM Class 3611 – 2004,
FM Class 3616 – 2011,
FM Class 3810 – 2005;
Markings
NI CL 1, DIV 2, GP A, B, C, D T4; Suitable for use in CL II, III, DIV 2, GP F, G T4;
T4(-40 °C ≤ T
a
≤ 60 °C)
Special Conditions for Safe Use(X)
1. When installed as Division 2 equipment, the Model 1410 Smart Wireless Gateway
shall be mounted within a tool-secured enclosure which meets the requirements of
ANSI/ISA 61010-1 and be capable of accepting the applicable wiring methods per
the NEC.
B.5.2
Canada
N6 Canada Division 2
Certificate
2646342 (CSA)
Standards
CAN/CSA C22.2 No. 0-10,
CSA C22.2 No. 213-M1987 (R2013),
CSA C22.2 No. 61010-1 - 2012,
ANSI/ISA-12.12.01 - 2012,
UL61010-1, 3rd Edition
Markings
Suitable for CL I, DIV 2, GP A, B, C, D;
T4 (-40 °C ≤ T
a
≤ 70 °C)
Note
• Shall be powered by a class 2 power supply.
• Suitable for dry indoor locations only.
• Equipment must be installed in a suitable tool accessible enclosure subject to the end
use application.
• Using the Emerson 1410D and the Smart Wireless Field Link 781 in a hazardous
location requires barriers between the two units.
B.5.3
Europe
N1 ATEX Type n
Certificate
Baseefa14ATEX0125X
Standards
EN 60079-0: 2012, EN 60079-15: 2010
Markings
II 3 G Ex nA IIC T4 Gc, T4(-40 °C ≤ T
a
≤ +75 °C), V
MAX
= 30 Vdc