ENGLISH
10
: Derivative Time. 0.0 to 999.9 second.If
this parameter can be observed. (Default: 25.0)
It can be adjusted from = ,then
: Output Control Period. 1 to 150 second
then this parameter can be observed. (Default: 10)
It can be adjusted from If = ,
: Proportional band . It can be adjusted from %1 to %100.If
this parameter can be observed. (Default: 10.0)
= , then
: If tune parameter is set to , device start to calculate PID parameters
automatically. This parameter is shown if = . (Default: )
: Integral Time. 0 to 3600 second.If
this parameter can be observed. (Default: 100)
It can be adjusted from = , then
: Process Type Selection. It can be or .(Default: )
: Process Control Type Selection. It can be or .(Default: )
: Hysteresis value. of the Scale
If = , then this parameter can be observed (Default: 3)
It can be adjusted from %0 ile %50 ( - )
: Sensor Break Output Value. %0 to %100. It can be adjusted from (Default: 0.0)
: Soft Start Control time. .
(Default:1)
This parameter determines soft start mode control time
: Soft Start Control Output. This parameter determines soft start mode control output
percentage. (Default: 10.0)
: Soft Start Set value. Device operates in Soft Start mode, until the temperature reaches
Soft Start set value. (Default: no)
: Control Menu Parameters
Note: If process input type selection( ) is changed, , ,
, , , , , , , , and
parameters may need to be updated according to the input type
selection.
: Alarm Hysteresis value. .
(Default: 0)
It can be adjusted from %0 ile %50 of the Scale( - )
: Alarm Type selection. (Default: )
:
Operation Scale maximum. (Default: 500)
Alarm Set High Limit parameter. It can be adjusted from Alarm Set Low Limit to
: Alarm on Delay Time. It can be adjusted from 0 to 9999 seconds. (Default: 0)
:
9998, , is seen on the screen and Alarm Latching Output is selected. (Default: 0)
Alarm off Delay Time. It can be adjusted from 0 to 9998 seconds. If it is higher than
:
Alarm Set High Limit. (Default: 0)
Alarm Set Low Limit parameter. It can be adjusted from Operation Scale minimum to
: Alarm Menu Parameters
: Process Set value Low Limit. Minimum set value is defined with this parameter. It
changes according to the process input type and scale. (Default: -200)
: Process Set value High Limit. Maximum set value is defined with this parameter.
It changes according to the process input type and scale. (Default: 900)
: Display offset for process value. It can be adjusted from -10% of scale to 10%
of scale. It is added to the process display value. (Default: 0)
: This parameter determines, which output will be Process control output. If rLY is
chosen, process output is relay output, if SSr is chosen, process output is SSR output.
(Default: Ssr)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EMKO ESM Series and is the answer not in the manual?

EMKO ESM Series Specifications

General IconGeneral
Control TypePID, On/Off
Input TypeThermocouple, RTD
Output TypeRelay, SSR, Analog
DisplayLED
Power Supply100-240V AC
Resolution0.1°C
CommunicationRS485
Dimensions48x48mm, 96x96mm

Related product manuals