Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 63
Customer Unit H/
CUSTOMER_HEIGHT_
UNIT
Selection
Index: 51
Data type: visible string
Access: auto, OOS
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also Cust. Unit. Fact. H/CUSTOMER_UNIT_FACTOR_HEIGHT.
Prerequisite:
• Comb. Measurand/COMBINED_MEASURAND = Height and volume,
Height Unit/HEIGHT_UNIT = User unit
• Comb. Measurand/COMBINED_MEASURAND = Height and mass,
Height Unit/HEIGHT_UNIT = User unit
• Comb. Measurand/COMBINED_MEASURAND = Height and %,
Height Unit/HEIGHT_UNIT = User unit
– Comb. Measurand = COMBINED_MEASURAND
– Height Unit = HEIGHT_UNIT
!
Note!
Only the first five characters are shown on the local operation. For example, if the customer-
specific unit "crates" was selected, only "crate" would be displayed.
If the unit contains a slash, up to eight characters can be shown on the local operation. The
maximum number of characters in the counter is again limited to five. For example if the
customer-specific unit "crates/m2" was selected, "crate/m2" would be displayed. In the
FF configuration program, the slash counts as a character, i.e. "crates/m2" would be
displayed as "crates/m".
Factory setting:
_ _ _ _ _ _ _ _
Cust. Unit. Fact. H/
CUSTOMER_UNIT_
FACTOR_HEIGHT
Entry
Index: 52
Data type: float
Access: auto, OOS
Enter the conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
→ See also Customer Unit H/CUSTOMER_HEIGHT_UNIT.
Prerequisite:
• Comb. Measurand/COMBINED_MEASURAND = Height and volume,
Height Unit/HEIGHT_UNIT = User unit
• Comb. Measurand/COMBINED_MEASURAND = Height and mass,
Height Unit/HEIGHT_UNIT = User unit
• Comb. Measurand/COMBINED_MEASURAND = Height and %,
Height Unit/HEIGHT_UNIT = User unit
– Comb. Measurand = COMBINED_MEASURAND
– Height Unit = HEIGHT_UNIT
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– Primary Value/PRIMARY_VALUE = 0.5 m i 1 PU
– Enter Customer Unit H/CUSTOMER_HEIGHT_UNIT: PU
– Enter Cust. Unit. Fact. H/CUSTOMER_UNIT_FACTOR_HEIGHT: 2
– Result: Primary Value/PRIMARY_VALUE = 1 PU
Factory setting:
1.0
Pressure Transducer Block
Parameter Description

Table of Contents