EasyManua.ls Logo

Endress+Hauser Cerabar S PMC71 - Page 85

Endress+Hauser Cerabar S PMC71
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cerabar S/Deltabar S/Deltapilot S FOUNDATION Fieldbus Parameter description (FF configuration program)
Endress+Hauser 85
Set. L. Fl. Cut-Off/
SET_LOW_FLOW_CUT_
OFF
Entry
Index: 20
Data type: Float
Access: read, write, OOS
Enter the switch-off point of low flow cut-off.
The hysteresis between the switch-on point and the switch-off point is always 1 % of the end
flow value. → ä 84, Low Flow Cut-Off/LOW_FLOW_CUT_OFF.
Prerequisite:
• Deltabar S differential pressure transmitter
• Low Flow Cut-Off/LOW_FLOW_CUT_OFF = On
Input range:
Switch-off point: 0 to 50% of end flow value (→ ä 58, parameter description for Scale Out/
SCALE_OUT, EU_100 element/MAX. FLOW)
P01-PMD7xxxx-05-xx-xx-xx-000
Factory setting:
5% (of end flow value)
Flow Max/MAX_FLOW
Entry
Index: 21
Data type: Float
Access: read, write, OOS
Enter maximum flow of primary device.
→ See also layout sheet of primary device. The maximum flow is assigned to the maximum
pressure which you enter via Max Press. Flow/MAX_PRESS_FLOW.
Factory setting:
1.0
Pressure/PRESSURE
Display
Index: 22
Data type: Float
Access: read only
Displays the measured pressure after sensor recalibration, position adjustment and damping.
This value corresponds to the Primary Value/PRIMARY_VALUE parameter in the "Pressure"
measuring mode.
P01-xMD7xxxx-05-xx-xx-en-011
Max Press. Flow/
MAX_PRESS_FLOW
Entry
Index: 23
Data type: Float
Access: read, write
Enter maximum pressure of primary device.
→ See layout sheet of primary device. This value is assigned to the maximum flow value
(
→ see Flow Max/MAX_FLOW).
Factory settings:
High sensor limit (
→ see PRESS. SENS HILIM, → ä 198)
Press. Eng. Unit/
PRESSURE_UNIT
Display
Index: 24
Data type: unsigned16
Access: read, write
Display the pressure unit selected.
The pressure unit is selected by means of the Calibration Units/CAL_UNIT parameter
(→ ä 54) in the Pressure Transducer Block.
DP Flow Transducer Block
Parameter Description
6%
5%
➀➁
0%
0%
Q
Q
max
Q
Q
max
Δp Δp
P
PV
Sensor
Analog
Input
Block
Pressure
Level
Flow
Damping
Position
adjust-
ment
Sensor
trim
Transducer Block
PRESSURE_1_
AFTER_DAMPING/
PRESSURE
PRESSURE_1_
AFTER_CALIBRATION/
CORRECTED PRESS.
PRESSURE_1_
AFTER_SENSOR/
SENSOR PRESSURE

Table of Contents