CM14 Wiring
Endress+Hauser 11
4 Wiring
!
WARNING
Danger from electrical voltage
The entire connection of the electrical system must take place while the device is de-
energized.
Danger if protective ground is interrupted
The protective ground connection must be established before any other connection is
made.
NOTICE
Thermal load of the lines
Use suitable lines for temperatures of 5 °C (9 °F) above ambient temperature.
Malfunction or destruction of the device due to incorrect supply voltage
Prior to commissioning, make sure the supply voltage matches the specifications on the
nameplate (bottom side of the housing).
Ensure the emergency shutoff of the device
Provide a suitable switch or power-circuit breaker in the building installation. This switch
must be provided within easy reach of the device and be labeled as a disconnector.
Protect device from overload
Provide a overload protection unit (rated current = 10 A) for the power supply line.
Incorrect wiring can cause destruction of the device
Observe the terminal designation on the rear of the device.
Energy-rich transients in long signal lines
Connect suitable upstream overvoltage protection in series.
It is permitted to connect a mixture of safety extra low voltage and voltage which poses a
shock hazard to the relays.