CM14 Technical data
Endress+Hauser 37
Orientation
The orientation is only determined by the legibility of the display.
Max. viewing angle +/- 45° in every direction from the central axis of the display.
92 (3.62)
45 (1.77)
A0010351
 6 Panel cutout, dimensions in mm (in)
11.8 Environment
11.8.1 Ambient temperature range
–10 to +60 °C (14 to 140 °F)
11.8.2 Storage temperature
–40 to +85 °C (–40 to +185 °F)
11.8.3 Operating height
< 2 000 m (6 561 ft) above MSL
11.8.4 Electromagnetic compatibility
Emitted interference and interference immunity to EN 61326-1:2006, Class A for industrial
areas
11.8.5 Degree of protection
Front
Front IP65 / NEMA 4X
Tube
Shock protection IP20
11.8.6 Relative humidity
5 to 85 %, non-condensing