Deltabar FMD71, FMD72 Description of device parameters
35
Edit table (042)
Navigation Expert → Measurement → Linearization → Edit Table (042)
Write permission Operators/Service engineers/Expert
Description Select the function for entering the table.
Options • Next point: enter the next point.
• Current point: stay on the current point to correct a mistake for example.
• Last input point: skip back to previous point to correct a mistake for example.
• Insert point: insert an additional point (see example below).
• Delete point: delete the current point (see example below).
Example Add point, in this case between the 4th and 5th point for example
• Select point 5 via the "Line-numb." parameter.
• Select the "Insert point" option via the "Edit table" parameter.
• Point 5 is displayed for the "Line-numb" parameter. Enter new values for the "X-val." and
"Y-val." parameters.
Delete point, in this case the 5th point for example
• Select point 5 via the "Line-numb." parameter.
• Select the "Delete point" option via the "Edit table" parameter.
• The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Factory setting Current point
Tank content (043)
Navigation Expert → Measurement → Linearization → Tank content (043)
Write permission Operators/Service engineers/Expert
Description Displays the level value after linearization.
Alarm Behav. P (050)
Navigation Expert → Output → Current Output → Alarm Behav. P (050)
Write permission Operators/Service engineers/Expert
Description Set current output if sensor module limits are overshot or undershot.