Deltabar FMD71, FMD72 Operation with an operating menu
11
Accepting the pressure present
Example: setting position adjustment.
Menu path: Main menu → Setup → Pos. Zero Adjust
Pos. Zero Adjust 007 Operation
1 Cancel The pressure for position adjustment is present at the device.
Confirm
2 Cancel Use or to switch to the "Confirm" option. The active option is
highlighted in black.
Confirm
3 Adjustment has
been accepted!
Accept the applied pressure as a position adjustment with the key. The
device confirms the adjustment and goes back to the "Pos. zero adjust"
parameter.
4 Cancel Exit edit mode for the parameter with .
Confirm
User-definable parameters
Example: setting parameter "Set URV (014)" from 100 mbar (1.5 psi) to 50 mbar (0.75
psi).
Menu path: Setup → Advanced. Setup → Current output → Set URV
Set URV 014 Operation
The onsite display shows the parameter to be changed. The "mbar" unit
is defined in another parameter and cannot be changed here.
1
1 0 0 . 0 0 0
mbar
Press or to get to edit mode. The first digit is highlighted in
black.
2
1 0 0 . 0 0 0
mbar
Use the key to change "1" to "5". Press the key to confirm "5".
Cursor jumps to the next position. Use the key to confirm (second
position).
3
5 0 0 . 0 0 0
mbar
The third digit is highlighted in black and can now be edited.
4
5 0 0 . 0 0 0
mbar
Use the key to change to the "¿" symbol. Use to save the new
value and exit edit mode. See next graphic.
5
5 0
¿
. 0 0 0
mbar
The new value for the full scale value is 50.0 mbar (0.75 psi). Exit edit
mode for the parameter with . You can get back to edit mode with
or .
6
5 0 . 0 0 0
mbar
2.5 Operation using Endress+Hauser operating program
The FieldCare operating program is an Endress+Hauser plant asset management tool
based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as
well as devices from other manufacturers that support the FDT standard.
Hardware and software requirements can be found on the Internet: