Deltabar FMD71, FMD72 Description of device parameters
31
Navigation Expert → Measurement → Level → Empty Pressure (029)/(185)
Write permission Operators/Service engineers/Expert
Description Enter the pressure value for the lower calibration point (vessel empty). See also "Empty
Calib. (028)".
Prerequisite "Level Selection" = In pressure
"Calibration mode" = Dry -> entry
"Calibration mode" = Wet -> display
Factory setting 0.0
Empty height (030)/(186)
Navigation Expert → Measurement → Level → Empty Height (030)/(186)
Write permission Operators/Service engineers/Expert
Description Enter the height value for the lower calibration point (vessel empty). The unit is selected
via the "Height unit (026)" parameter.
Prerequisite "Level Selection" = "In height"
"Calibration mode" = Dry -> entry
"Calibration mode" = Wet -> display
Factory setting 0.0
Full Calib. (031)/(012)
Navigation Expert → Measurement → Level → Full Calib. (031)/(012)
Write permission Operators/Service engineers/Expert
Description Enter the output value for the upper calibration point (vessel full). The unit defined in "Unit
Before Lin." must be used.
Note In the case of wet calibration, the level (vessel full) must actually be available. The
associated pressure is then automatically recorded by the device.
In the case of dry calibration, the level (vessel full) does not have to be available. The
associated pressure has to be entered in the "Full Pressure" parameter for the "In pressure"
level selection. The associated height has to be entered in the "Full height" parameter for
the "In height" level selection.
Factory setting 100.0
Full Pressure (032)/(187)