Description of device parameters Deltabar FMD71, FMD72
34
Options • %
• cm, dm, m, mm
• hl
• in
3
, ft
3
, m
3
,
• l
• in, ft
• kg, t
• lb
• gal
• Igal
Factory setting %
Line numb. (039)
Navigation Expert → Measurement → Linearization → Line-numb. (039)
Write permission Operators/Service engineers/Expert
Description Enter the number of the current point in the table. The subsequent entries in "X-val." and
"Y-val." refer to this point.
Input range 1...32
X-value (040)/(123)/(193)
Navigation Expert → Measurement → Linearization → X-value (040)/(123)/(193)
Write permission Operators/Service engineers/Expert
Description Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note • If "Lin. mode" = "Manual", the level value must be entered.
• If "Lin. mode" = "Semiautomatic", the level value is displayed and has to be confirmed by
entering the paired Y-val.
Y-val (041)/(194)
Navigation Expert → Measurement → Linearization → Y-val (041)/(194)
Write permission Operators/Service engineers/Expert
Description Enter the Y-val (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin."
Note The linearization table must be monotonic (increasing or decreasing).