Deltabar FMD71, FMD72 Description of device parameters
49
Navigation Expert → Output → Current output → Offset trim 20mA (138)
Write permission Service engineers/Expert
Description Display/enter the difference between 20 mA and the value entered for the parameter
"Curr. trim 20mA".
Factory setting 0
Description (139)
Navigation Expert → Communication → HART info → Description (139)
Write permission Service engineers/Expert
Description Enter the tag description (max. 16 alphanumeric characters)
HART message (140)
Navigation Expert → Communication → HART info → HART message (140)
Write permission Service engineers/Expert
Description Enter the message (max. 32 alphanumeric characters) Upon request from the master, this
message is sent via the HART protocol.
HART date (141)
Navigation Expert → Communication → HART info → HART date (141)
Write permission Service engineers/Expert
Description Enter the date of the last configuration change.
Factory setting DD/MM/YY (date of the final test)
Burst Mode (142)
Navigation Expert → Communication → HART config → Burst Mode (142)
Write permission Service engineers/Expert