Description of device parameters Deltabar FMD71, FMD72
58
Description Displays HART version 6.
High Press. Side (183)
Navigation Expert → Measurement → Pressure → High Press. Side (183)
Write permission Operators/Service engineers/Expert
Description Define which sensor module corresponds to the high-pressure side.
Options • Sensor HP
• Sensor LP
Factory setting Sensor HP
Current at alarm (051)/(190)
Navigation Expert → Output → Current output → Current at alarm (051)/(190)
Write permission Operators/Service engineers/Expert
Description Select Output fail mode. In case of an alarm, the current and the bargraph assume the
current value specified with this parameter.
Options • Max: can be set from 21 to 23 mA
• Hold: last measured value is held.
• Min: 3.6 mA
Factory setting Max (22 mA)
Cust. tag number (254)
Navigation Expert → System → Instrument info → Cust. tag number (254)
Write permission Operators/Service engineers/Expert
Description Enter the device tag, e.g. TAG number (max. 8 alphanumeric characters).
Factory setting No entry or according to order specifications
COUNTER P < Pmin (262)