Deltabar S
Endress+Hauser 17
4. Switch the device off and on again. This ensures that the parameter settings are saved.
5. Check safety functions ("Checks", ä 22).
Restart FieldCare/DeviceCare or Handheld FieldCommunicator and reconnect device.
6. Select the "SAFETY CONFIRM." group.
(Menu path: (GROUP SELECTION ) OPERATING MENU SAFETY CONFIRM.).
7. Select the "Lock" option.
Select the "Lock" option via the SAFETY LOCK parameter. The status "Locked" or "Unlocked" is
indicated on the fourth line on the display.
8. Enter the password via the SAFETY PASSWORD parameter (password: 7452).
Record the following confirmed settings according to the "Form for device configuration" (column
"Read-out actual value", ä 33ff).
9. By means of the DIGIT SETS parameter, the user checks whether the characters and digits are
displayed correctly on the user interface. "0123456789.-" is displayed if everything is displayed
correctly.
Options:
– Valid: Select this option if the string of characters and digits is displayed correctly.
– Not valid: Select this option if the string of characters and digits is not displayed correctly. In
this case, operation in the safe measuring mode is not possible. The confirmation sequence is
aborted.
SET LRV X X X BASIC SETUP
SET URV X X X BASIC SETUP
DAMPING VALUE X X X BASIC SETUP
OUPUT FAIL MODE
2)
X X X OUTPUT
SET MIN. CURRENT
X X X OUTPUT
SET MAX. ALARM
X X X OUTPUT
E727 P.OVERRANGE
X X X OUTPUT
1) Not for options with 160/250 bar measuring range (2320/3625 psi)
2) From firmware version ≥ 2.30
The PRESSURE EMPTY and PRESSURE FULL parameters are only displayed for the "Dry"
CALIBRATION MODE. If you have performed a wet calibration, you subsequently have to
select the "Dry" option by means of the CALIBRATION MODE parameter.
You can read out the corresponding values for the PRESSURE EMPTY and PRESSURE FULL
parameters here.
For firmware version ≤ 02.20.04
– If the correct password is entered, the following
parameters are reset to the factory values:
CURR. CHARACT., OUTPUT FAIL MODE, ALT.
CURR. OUTPUT., SET MAX. ALARM, SET MIN.
CURRENT, SIMULATION MODE, ALARM DELAY,
ALARM DISPL. TIME and SELECT ALARMTYPE
( Point 10 for factory values).
– Any simulation running is terminated.
– The configurable messages ("Error"-type messages)
115, 120, 620, 715, 717, 718, 720, 726, 727 are
automatically set to "Alarm".
Operating Instructions BA00270P/00/EN,
"Messages" section.
For firmware version ≥ 02.30.zz
– Any simulation running is terminated.
– No parameters are reset.
Parameters Available in the operating mode Group
Pressure Level, "Level
Easy Pressure"
level selection
Flow
1)