Deltabar S PROFIBUS PA Operation
Endress+Hauser 21
6.2.2 Function of the operating elements – on-site display not connected
Operating key(s) Meaning
P02-xxxxxxxx-19-xx-xx-xx-107
Position adjustment (zero point correction): Press key for at least 3 seconds. If the
LED on the electronic insert lights up briefly, the pressure applied has been
accepted for position adjustment.
See also Page 32 (Pressure measuring mode), Page 36 (Level measuring mode)
or Page 38 (Flow measuring mode).
Total reset: Press key for at least 12 seconds. If the LED on the electronic insert
lights up briefly, the reset is being carried out.
P01-xxxxxxxx-19-xx-xx-xx-109
Set address in the bus. See also Page 27, Section 4.4 "Configuring the device
address".
P01-xxxxxxxx-19-xx-xx-xx-108
DIP-switch 1: for locking/unlocking measured-value-relevant parameters
Factory setting: off (unlocked)
DIP switch 2: damping on/off
Factory setting: on (damping on)
0%
Zero
on
off
12
3
4
5
67 8
Address
21
CKON
34 5 67 8
SDA0 8
01
SW
HW
1
2
on
off
τ