Commissioning Deltabar S PROFIBUS PA
34 Endress+Hauser
7.4.1 Quick Setup menu for Level measuring mode – on-site display
• Some parameters are only displayed if other parameters are appropriately configured (see the
following table).
• The following parameters are set to the following values in the factory:
– LEVEL SELETION: Level Easy Pressure
–CALIBRATION MODE: Wet
– OUTPUT UNIT or LIN. MEASURAND: %
– EMPTY CALIB.: 0.0
– FULL CALIB.: 100.0
• For parameter description see Operating Instructions BA00296P.
• The quick setup is suitable for simple and quick commissioning. If you wish to make more
complex settings, e.g. change the unit from "%" to "m", you will have to calibrate using the
BASIC SETTINGS group.
• See also Page 22, Section 4.2.3 "Function of the operating elements" and Page 23, 4.3 "On-site
operation via on-site display".
P01-xMD7xxxx-19-xx-xx-xx-075
Fig. 12: Quick Setup menu for Level measuring mode
1)
1)
1) – LEVELSELECTION "Level Easy Pressure"
and CALIBRATION MODE "Wet"
– LEVELSELECTION = "Level Standard",
LEVEL MODE = "Linear" and
CALIBRATION MODE ="Wet"
POS. ZERO ADJUST
EMPTY CALIB.
FULL CALIB.
DAMPING VALUE
Flow
Pressure
Level
MEASURED VALUE
QUICKSETUPLANGUAGE
OPERATING MENUMEASURING MODE
GROUPSELECTION
LEVELSELECTION
On-site operation
Measured value display
On-site display: Switch from the measured value display to GROUP SELECTION with F.
GROUP SELECTION
Select MEASURING MODE.