Deltapilot M 4...20 mA HART Commissioning
Endress+Hauser 53
8.7.2 Calibration with reference pressure (wet calibration)
Example:
In this example, a device with a 400 mbar (6 psi) sensor is configured for the 0 to +300 mbar
(4.5 psi) measuring range, i.e. 0 mbar is assigned to the 4 mA value and 300 mbar (4.5 psi) to
the 20 mA value.
Prerequisite:
The pressure values 0 mbar and 300 mbar (4.5 psi) can be specified. The device is already
mounted, for example.
For a description of the parameters mentioned, see operating instructions "Description of
parameters".
Description
1 Select the "Pressure" measuring mode via the
"Measuring mode" parameter.
Menu path: Setup Measuring mode
A0031032
Fig. 19: Calibration without reference pressure
A See Table, Step 3.
B See Table, Step 4.
2 Select a pressure unit via the "Press eng. unit"
parameter, here "mbar" for example.
Menu path: Setup Press. eng. unit
3 Select the "Set LRV" parameter.
Menu path: Setup Set LRV
Enter the value for the "Set LRV" parameter (here 0
mbar) and confirm. This pressure value is assigned
to the lower current value (4 mA).
4 Select the "Set URV" parameter.
Menu path: Setup Set URV
Enter the value for the "Set URV" parameter (here
300 mbar (4.5 psi)) and confirm. This pressure
value is assigned to the upper current value
(20 mA).
5Result:
The measuring range is configured for 0 to +300
mbar (4.5 psi).